DCSA50
ActiveTRANSDUCER CURRENT 10-30VDC

DCSA50
ActiveTRANSDUCER CURRENT 10-30VDC
Technical Specifications
Parameters and characteristics for this part
| Specification | DCSA50 |
|---|---|
| Accuracy | 0.25 % |
| Approval Agency | UL, CSA, CE |
| Input Range [Max] | 50 mA |
| Input Range [Min] | 0 A |
| Mounting Type | DIN Rail |
| Operating Temperature [Max] | 60 °C |
| Operating Temperature [Min] | -30 ░C |
| Output [Max] | 20 mA, 10 V |
| Output [Min] | 4 mA, 1 V |
| Response Time | 300 ms |
| Termination Style | Screw Terminal |
| Type | Current Transducer |
| Voltage - Supply [Max] | 30 VDC |
| Voltage - Supply [Min] | 10 VDC |
Pricing
Prices provided here are for design reference only. For realtime values and availability, please visit the distributors directly
Description
General part information
DCSA50 Series
The DCSA Series is a loop-powered, linear output current transducer that provides an output that is directly proportional to the RMS AC current passing through the LCSC10T12 sensor. The DCSA provides either an analog current or voltage: 4 - 20 mA, 1 to 5VDC, or 2 to 10VDC. Each unit is factory calibrated for monitoring (with the LCSC10T12 connected) in one of four ranges; 0 - 5, 0 - 10, 0 - 20, or 0 - 50A. Zero and span adjustments allow field calibration if needed. The DCSA mounts on both DIN 1 and DIN 3 rails. See datasheet for operation details.