ECS20BC
ActiveRELAY CUR SENSE 24VAC 0.5-5A

ECS20BC
ActiveRELAY CUR SENSE 24VAC 0.5-5A
Technical Specifications
Parameters and characteristics for this part
| Specification | ECS20BC |
|---|---|
| Contact Rating @ Voltage | 10 A, 240 VAC |
| Delay Time [Max] | 50 Sec |
| Delay Time [Min] | 0.5 Sec |
| Mounting Type | Chassis Mount |
| Operating Temperature [Max] | 60 °C |
| Operating Temperature [Min] | -40 °C |
| Trip Range [Max] | 5 A AC |
| Trip Range [Min] | 0.5 A AC |
| Trip Status | Energized High/Low |
| Type | Current Sensing AC |
| Voltage - Supply | 24 VAC |
Pricing
Prices provided here are for design reference only. For realtime values and availability, please visit the distributors directly
Description
General part information
ECS20BC Series
The ECS Series of single-phase AC current sensors is a universal, overcurrent or undercurrent sensing control. Its built-in toroidal sensor eliminates the inconvenience of installing a stand-alone current transformer. Includes onboard adjustments for current sensing mode, trip point, and trip delay. Detects over or undercurrent events like locked rotor, loss of load, an open heater or lamp load, or proves an operation is taking place or has ended. Operation Input voltage must be supplied at all times for proper operation. When a fault is sensed throughout the trip delay, the output relay is energized. When the current returns to the normal run condition or zero, the output and the delay are reset. If a fault is sensed and then corrected before the trip delay is completed, the relay will not energize and the trip delay is reset to zero.