ECSW4MBHT
ActiveRELAY CUR SENSE 120VAC 2-20A
Deep-Dive with AI
Search across all available documentation for this part.

ECSW4MBHT
ActiveRELAY CUR SENSE 120VAC 2-20A
Deep-Dive with AI
Technical Specifications
Parameters and characteristics for this part
| Specification | ECSW4MBHT |
|---|---|
| Contact Rating @ Voltage | 10 A, 240 VAC |
| Delay Time [Max] | 50 Sec |
| Delay Time [Min] | 0.5 Sec |
| Mounting Type | Chassis Mount |
| Operating Temperature [Max] | 60 °C |
| Operating Temperature [Min] | -40 °C |
| Trip Range [Max] | 20 mA DC |
| Trip Range [Min] | 2 klux |
| Trip Status | Energized High/Low |
| Type | Current Sensing AC |
| Voltage - Supply | 120 VAC |
Pricing
Prices provided here are for design reference only. For realtime values and availability, please visit the distributors directly
Description
General part information
ECSW4MBHT Series
The ECSW Series of single-phase, AC window, current sensors includes adjustable overcurrent and undercurrent trip points. Detects locked rotor, jam, loss of load, an open heater or lamp load, a broken belt, or loss of suction. LED’s aid in trip point adjustment and provide fault indication. The built-in toroidal sensor eliminates the need for an external current transformer. The output can be electrically latched after a fault, or automatically reset. Remote resetting of a latched output by removing input voltage. The unit includes switch selectable zero current detection and normally de-energized or energized output operation. Time delays are included to improve operation and eliminate nuisance tripping. See datasheet for operation detail.
Documents
Technical documentation and resources