PLR240A
Active3 PHASE LINE MONITOR/ BOX

PLR240A
Active3 PHASE LINE MONITOR/ BOX
Technical Specifications
Parameters and characteristics for this part
| Specification | PLR240A |
|---|---|
| Contact Rating @ Voltage | 5 A, 240 VAC |
| Delay Time | False |
| Mounting Type | Chassis Mount |
| Trip Range [Max] | 270 V AC |
| Trip Range [Min] | 190 V AC |
| Trip Status | Energized Low |
| Type | Voltage Sensing AC |
| Voltage - Supply [Max] | 270 VAC/DC |
| Voltage - Supply [Min] | 190 VAC |
Pricing
Prices provided here are for design reference only. For realtime values and availability, please visit the distributors directly
Description
General part information
PLR240A Series
The PLR Series provides a cost effective means of preventing 3-phase motor startup during adverse voltage conditions. Proper A-B-C sequence must occur in order for the PLR’s output contacts to energize. In addition, the relay will not energize when an undervoltage or phase loss condition is present. The PLR protects a motor against undervoltage operation. The adjustment knob sets the undervoltage trip point. Operation The output relay is energized and the LED glows when all voltages are acceptable and the phase sequence is correct. Undervoltage must be sensed for a continuous dropout delay period before the relay de-energizes. Reset is automatic upon correction of the fault condition. The output relay will not energize if a fault condition is sensed as power is applied.