Zenode.ai Logo
Beta
201a-au-ot-al-2
Industrial Automation and Controls

201A-AU-OT

Active
Littelfuse/Commercial Vehicle Products

3-PH PLUG-IN VM/190-480V/ADJ./ BOX

Deep-Dive with AI

Search across all available documentation for this part.

201a-au-ot-al-2
Industrial Automation and Controls

201A-AU-OT

Active
Littelfuse/Commercial Vehicle Products

3-PH PLUG-IN VM/190-480V/ADJ./ BOX

Deep-Dive with AI

Technical Specifications

Parameters and characteristics for this part

Specification201A-AU-OT
Contact Rating @ Voltage10 A, 240 VAC
Delay Time1 Sec
Delay Time [Max]30 Sec
Delay Time [Min]1 Sec
Mounting TypeSocketable
Operating Temperature [Max]70 °C
Operating Temperature [Min]-40 °C
Trip Range [Max]480 V AC
Trip Range [Min]190 V AC
Trip StatusEnergized High/Low
TypeVoltage Asymmetry, Voltage Sensing AC

Pricing

Prices provided here are for design reference only. For realtime values and availability, please visit the distributors directly

DistributorPackageQuantity$
DigikeyBulk 1$ 171.84
10$ 134.07
25$ 120.76
50$ 111.26
NewarkEach 1$ 159.97
5$ 153.14
10$ 137.54
25$ 132.66
50$ 130.71
100$ 127.78

Description

General part information

201A-AU-OT Series

The 201A-AU is a 3-phase, auto-ranging, dual-range voltage monitor that protects 190-480VAC, 50/60Hz motors regardless of size. Has user adjustable 1-30 second trip delay, manual or 1-500 second restart delay, and 2-8% voltage unbalance trip point. The product also provides a user selectable nominal voltage setpoint and the voltage monitor automatically selects between the 200V and 400V range. The Model 201A-AU includes advanced single LED diagnostics, where five different light patterns distinguish between faults and normal conditions. This unique microcontroller-based voltage and phase-sensing device constantly monitors the 3-phase voltages to detect harmful power line conditions. When a harmful condition is detected, the 201A-AU's output relay is deactivated after a specified trip delay. The output relay reactivates after power line conditions return to acceptable levels.