201-575-AU-OT
Active3-PH PLUG-IN VM/ 575V/ ADJ. VU/ BOX
Deep-Dive with AI
Search across all available documentation for this part.

201-575-AU-OT
Active3-PH PLUG-IN VM/ 575V/ ADJ. VU/ BOX
Deep-Dive with AI
Technical Specifications
Parameters and characteristics for this part
| Specification | 201-575-AU-OT |
|---|---|
| Contact Rating @ Voltage | 10 A, 240 VAC |
| Delay Time | 1 Sec |
| Delay Time [Max] | 30 Sec |
| Delay Time [Min] | 1 Sec |
| Mounting Type | Socketable |
| Operating Temperature [Max] | 70 °C |
| Operating Temperature [Min] | -40 °C |
| Trip Range [Max] | 600 V AC/DC |
| Trip Range [Min] | 475 V AC |
| Trip Status | Energized High/Low |
| Type | Voltage Asymmetry, Voltage Sensing AC |
| Voltage - Supply [Max] | 600 VAC |
| Voltage - Supply [Min] | 475 VAC |
Pricing
Prices provided here are for design reference only. For realtime values and availability, please visit the distributors directly
Description
General part information
201-575-AU-OT Series
The 201A-AU is a 3-phase, auto-ranging, dual-range voltage monitor that protects 190-480VAC, 50/60Hz motors regardless of size. Has user adjustable 1-30 second trip delay, manual or 1-500 second restart delay, and 2-8% voltage unbalance trip point. The product also provides a user selectable nominal voltage setpoint and the voltage monitor automatically selects between the 200V and 400V range. The Model 201A-AU includes advanced single LED diagnostics, where five different light patterns distinguish between faults and normal conditions. This unique microcontroller-based voltage and phase-sensing device constantly monitors the 3-phase voltages to detect harmful power line conditions. When a harmful condition is detected, the 201A-AU's output relay is deactivated after a specified trip delay. The output relay reactivates after power line conditions return to acceptable levels.